Description of Contract
One (1) Year full coverage
Emergency Service 7x24, 365
Including all parts, labor and expenses
Response time is four (4) hours or less
Contract includes two (2) PM Inspections
  • To be performed during normal business hours
  • Includes full UPS Electronics & Battery maintenance
  • Battery replacement not covered under contract
UPS Preventive Maintenance – Detailed Check List
Visual Checks
  • Insulation, Overheating, Damage
Cleaning/Air Flow
  • Check fans, Door/Compartment Seals
  • Replace Filters (Customer Supplied)
  • Clean Module
Check/Record Voltage Waveforms And Currents
  • Input/Output, Rectifier, AC&DC Caps
Power Measurements (On Line)
  • Output RMS Current (Phase and Neutral)
  • Output Peak Current (Phase and Neutral)
Metering
  • DC Volts And Current
  • Input volts/Current
  • Output Volts/Current
  • Frequency
Fuses
  • Verify Type, value, condition
Synchronizing
  • Verify Utility Sync & Transfer To Bypass
  • Transfer From Bypass To UPS
  • Verify Voltage And Phase Lockout
  • Verify Static Bypass Operation
Control Calibrations
  • Check/Adjust as necessary
Circuit Breakers/Isolators
  • Verify Free Travel
  • Check Mag/Thermal Settings
System/Module Safety Parameters
  • Check Battery Current Limit *
  • Check Input Current Limit *
  • Check Overload Levels *
  • Check Overtemp Circuits *

* Where possible/available

Battery Preventive Maintenance – Detailed Check List
  • Perform safety evaluation of battery, racks, protective equipment and environment. Note and record any discrepancies.
  • Record the ambient temperature of the battery room.
  • Clean normal cell dirt/dust accumulation. Note: Some environments may not allow for practical management of dust accumulation.
  • Inspect each jar for signs of cracks, excessive bulging and leakage.
  • Measure and record the full string charging voltage and current.
  • Measure and record the AC ripple voltage and current.
  • Measure and record the voltage to ground for each string/cabinet.
  • Measure and record the float voltage across each cell/jar.
  • Measure and record the conductance of each cell/jar.
  • Check for corrosion on battery terminals and connectors. Clean as necessary.